MCR SVC Specification and Installation
MCR SVC Specification and Installation

Specification and Installation of MCR SVC

Specification
Capacity kVAR L×W×H
mm
Weight
kg
Cooling Mode Radiator
630 2500×660×1280 4180 Air cooling (dry-type) Fan (Back up)
1250 2800×800×1280 6990
2000 3200×1000×1360 10020
3150 3600×1000×1600 13000
5000 4000×1200×1800 16900 Oil cooling (oil-immersed type) Oil-immersed self-cool and fan cooling
6300 4500×1600×2200 21600
10000 6000×1800×2600 26000
20000 7000×2000×2800 16000×3
30000 7600×2200×2800 22000×3
50000 8500×2400×2800 28000×3
80000 9000×2500×2800 39000×3

Note: 1. Product will be re-designed if the required compensation capacity is over 80000 kVAR, and the dimension of unit capacity will be reduced.
2. The above data are just for reference. The actual dimensions may have a little difference.

Installation
Oil-immersed reactor can be installed indoors or outdoors, and dry-type reactor is usually installed indoors;
The thyristor cabinet should be installed in the indoor and close to the reactor;
The capacitor bank can be installed outdoors or indoors.